Rated Voltage: |
400V |
Rated Capacity: |
30~100kVAr/15~150A |
Frequency Circuit: |
50/60Hz±5% |
Circuit Topology: |
Three Level |
Multi Compensation Mode: |
Harmonic compensation, reactive compensation, three-phase load unbalance compensation |
Filter range Rated of: |
2nd~51st odd order harmonics (Selective or Full compensation) |
Related Harmonic Reduction: |
≥97.5% (For typical harmonic order distortions) |
Filtering Performance: |
Typically, THDi≤ 5% at rated load(Even with most complex loads) |
Target Power Factor: |
Adjustable from -1.0 to +1.0 |
3 Phase Load Balancing Effect: |
≤5%, Mitigate negative and zero sequence |
Neutral Filtering Capacity: |
3 times the rated filter current(in case of 4 wire device) |
3 Phase Load Balancing Effect: |
≤5%, Mitigate negative and zero sequence |
Neutral Filtering Capacity: |
3 times the rated filter current(in case of 4 wire device) |
Switching/control frequency : |
25.6kHz |
Initial response time: |
≤50us |
Overall response time: |
≤5ms |
Active loss of system: |
≤2.5% |
Output current limit : |
Automatically limited within 100% of rated capacity to output |
Control algorithm: |
Intelligent FFT,Self-adaptive control algorithm(ADALINE), fast Fourier (FFT) and instantaneous reactive power algorithm |
Controller: |
DSP+FPGA |
Protection: |
Hardware protection, Software protection |
Control connection: |
Fibre or electrical connection |
Human Machine Interface: |
4.3’’inch/7’’inch/10’’inch touched TFT LCD HMI |
Communication protocols: |
Adopt Modbus RTU remote communication protocol; Communication interface adopts two channel RS485 and
CAN bus, Supporting mobile phone APP operation, Accessing and monitioring via Ethernet
|
Noise: |
<60db(<45db during low-speed operation) |
Installation method: |
Module embedded(Rack),wall mounted, free landing |
Level of protection: |
IP42 |
Cooling method: |
Speed regulation intelligent air cooling PWM Fans |
Color: |
RAL 7035 Light Grey/Black |
Ambient temperature: |
-20~55℃ |
Relative humidity: |
Maximum 95%, without condensation |
Mounting height above sea level: |
≤2000 at rated capacity; appropriately reduce the capacity if it is > 2000(1% derating per 100m) |
Qaulifications: |
CE, IEEE61000,Type Test Report, ISO9001:2015 |
Compliance with Standards: |
IEEE 519, ERG5/4 |